AAON · model number decoder

AAON RN Series

AAON's configurable RN rooftop line, built to order from a long feature string. The first 25 characters tell you the size, cabinet, voltage, compressor and condenser type, cooling staging and heat type.

Packaged rooftop unit, heat pump or outdoor air unit · 6–70 tons · R-454B

Decoded against AAON’s published nomenclature. Characters we can’t match are flagged, not guessed. What you type stays in this tab.

Sizes and filter sizes

Size codeNominal tonsUnit filters (standard 2 in. pleated MERV 8)
0066(4) 16 x 20 x 2 in.
0077(4) 16 x 20 x 2 in.
0088(4) 16 x 20 x 2 in.
0099(4) 20 x 25 x 2 in.
01010(4) 16 x 20 x 2 in.
01111—
01313—
01616(6) 20 x 25 x 2 in.
01818(6) 20 x 25 x 2 in.
02020(6) 20 x 25 x 2 in.
02525(6) 20 x 25 x 2 in.
02626(8) 24 x 24 x 2 in.
03030(6) 20 x 25 x 2 in.
03131(8) 24 x 24 x 2 in.
04040(8) 24 x 24 x 2 in.
05050(24) 12 x 24 x 2 in.
06060(24) 12 x 24 x 2 in.
07070(24) 12 x 24 x 2 in.

Source: RN Series IOM 20260615, pages 25, 132, 135. Factory filter sizes. Check the rack before ordering; filters get changed over the years.

AAON RN Series model number nomenclature

Example: RNA-010-A-A-3-FAA02-CA1B0. Select a position to jump to its codes.

Position 4 is always “-” (separator). Position 8 is always “-” (separator). Position 10 is always “-” (separator). Position 12 is always “-” (separator). Position 14 is always “-” (separator). Position 20 is always “-” (separator). The decoder works with or without it.

Position 1–2 Series and generation

RNAAON RN Series

RN Series IOM 20260615, page 25

Position 3 Major revision

AMajor revision A

RN Series IOM 20260615, page 25

Position 5–7 Unit size (nominal tons)

0066 tons
0077 tons
0088 tons
0099 tons
01010 tons
01111 tons
01313 tons
01616 tons
01818 tons
02020 tons
02525 tons
02626 tons
03030 tons
03131 tons
04040 tons
05050 tons
06060 tons
07070 tons

RN Series IOM 20260615, page 25

Position 9 Series (cabinet)

AA cabinet: 6–8 and 10-ton units
BB cabinet: 9 and 11–15-ton units
CC cabinet: 11–25 and 30-ton units
DD cabinet: 26, 31, 40, 50, 60 and 70-ton units

RN Series IOM 20251205, page 17

Position 11 Minor revision

AMinor revision A

RN Series IOM 20260615, page 25

Position 13 Voltage

1230 V, single phase, 60 Hz
2230 V, three phase, 60 Hz
3460 V, three phase, 60 Hz
4575 V, three phase, 60 Hz
6380 V, three phase, 60 Hz
8208 V, three phase, 60 Hz
9208 V, single phase, 60 Hz

RN Series IOM 20260615, page 25

Position 15 A1: Compressor style

0No compressor
FR-454B two-step scroll compressor
GR-454B digital scroll compressor
HR-454B variable-speed scroll compressor
KR-454B refrigerant-injection variable-speed compressor

RN Series IOM 20260615, page 26

Position 16 A2: Condenser style

0No condenser
AMicrochannel air-cooled condenser
FWater-cooled condenser
JAlpha Class air-source heat pump (cold-climate version when A1 = H)
LWater-source / geothermal heat pump
NDX air handling unit

RN Series IOM 20260615, page 26

Position 17 A3: Indoor coil configuration

0No cooling coil
AStandard evaporator
B6-row evaporator
E4-row chilled water coil
F6-row chilled water coil

RN Series IOM 20260615, page 26

Position 18 A4: Cooling coil construction

0Standard
APolymer e-coated cooling coil
BStainless-steel cooling coil casing
DE-coated cooling coil and stainless-steel coil casing
EPolymer e-coated condenser coil
JPolymer e-coated evaporator and condenser coils
TStainless-steel coil casing with e-coated evaporator and condenser coils

RN Series IOM 20260615, page 26

Position 19 A5: Cooling staging

0No cooling
22-stage cooling
44-stage cooling
55-stage cooling
66-stage cooling
AVariable capacity. Smaller units: variable on/off; larger units add tandem on/off compressors (arrangement depends on size)
BTwo variable-capacity compressors on 11–25 and 30-ton units; larger units add fixed or two-step compressors
CVariable-capacity compressor plus a two-step compressor (size dependent)
FChilled water coil: single serpentine, 8 fins per inch
GChilled water coil: half serpentine, 8 fins per inch
HChilled water coil: single serpentine, 10 fins per inch
JChilled water coil: half serpentine, 10 fins per inch
KChilled water coil: single serpentine, 12 fins per inch
LChilled water coil: half serpentine, 12 fins per inch
RHeat pump with low-ambient heating
SHeat pump with ultra-low-ambient heating

RN Series IOM 20260615, page 26

Position 21 B1: Heating type

0No heat
AElectric heat
BElectric heat (RN horizontal)
CNatural gas
DNatural gas (RN horizontal)
FLP gas
GLP gas (RN horizontal)
JHot water coil
KHot water coil (RN horizontal)
LSteam distributing coil
MSteam distributing coil (RN horizontal)

RN Series IOM 20260615, page 27

Position 22 B2: Heat construction

0Standard
AAluminum heat exchanger, gas piping to the valve
BStainless-steel heat exchanger, gas piping to the valve
CHigh-altitude aluminum heat exchanger, gas piping to the valve
DHigh-altitude stainless-steel heat exchanger, gas piping to the valve
GPolymer e-coated heating coil
HStandard-CFM electric heat
JLow-CFM electric heat

RN Series IOM 20260615, page 27

Position 23 B3: Heat designation

0No heat
1Heat size 1 (capacity depends on unit size and heat type)
2Heat size 2 (capacity depends on unit size and heat type)
3Heat size 3 (capacity depends on unit size and heat type)
4Heat size 4 (capacity depends on unit size and heat type)
5Heat size 5 (capacity depends on unit size and heat type)
6Heat size 6 (capacity depends on unit size and heat type)
7Heat size 7 (capacity depends on unit size and heat type)
A1-row heating coil
E2-row heating coil

RN Series IOM 20260615, page 27

Position 24 B4: Heating staging

0No heat
A1 stage
B2 stages
C3 stages
D4 stages
E5 stages
F6 stages
G7 stages
H8 stages
J12 stages
KModulating gas heat, temperature control
LHigh-turndown modulating gas heat, temperature control
MModulating SCR electric heat with temperature control
NModulating SCR electric heat: AAON temperature control, or 0–10 VDC from controls by others
PHeating coil: single serpentine, 8 fins per inch
QHeating coil: half serpentine, 8 fins per inch
RHeating coil: single serpentine, 10 fins per inch
SHeating coil: half serpentine, 10 fins per inch
THeating coil: single serpentine, 12 fins per inch
UHeating coil: half serpentine, 12 fins per inch
V10 stages

RN Series IOM 20260615, page 28

Position 25 B5: Heat pump auxiliary heat

0No heat pump
1Aux heat 6 for 4-stage heat pump
2Aux heat 7 for 4-stage heat pump
AAux heat 1 for 1-stage heat pump
BAux heat 2 for 1-stage heat pump
CAux heat 3 for 1-stage heat pump
DAux heat 4 for 1-stage heat pump
EAux heat 5 for 1-stage heat pump
FAux heat 6 for 1-stage heat pump
GAux heat 7 for 1-stage heat pump
KAux heat 1 for 2-stage heat pump
LAux heat 2 for 2-stage heat pump
MAux heat 3 for 2-stage heat pump
NAux heat 4 for 2-stage heat pump
PAux heat 5 for 2-stage heat pump
QAux heat 6 for 2-stage heat pump
RAux heat 7 for 2-stage heat pump
UAux heat 1 for 4-stage heat pump
VAux heat 2 for 4-stage heat pump
WAux heat 3 for 4-stage heat pump
YAux heat 4 for 4-stage heat pump
ZAux heat 5 for 4-stage heat pump

RN Series IOM 20260615, page 28

What this page doesn’t cover

  • Decodes the first 25 characters of the current R-454B RN feature string (for example RNA-010-A-A-3-FAA02-CA1B0): base model, Model Option A (cooling) and Model Option B (heating). The rest of the string (after the colon: controls, economizer, filters, energy recovery and other features) is not decoded here; check it against AAON's IOM.
  • AAON's own sample string in the IOM uses a compressor code (C) that is not in the current compressor list, so our example is assembled from listed codes rather than copied.
  • The cabinet series letters (position 9) come from the December 2025 edition of the IOM; the June 2026 Rev B edition still shows the position but drops its legend. The two editions overlap for 11–15-ton units (B and C cabinets).
  • Older R-410A RN units use a different model layout (for example RN-025-3-0-...). This decoder does not read those strings.
  • Cooling staging codes A, B and C mean different compressor arrangements at different sizes; AAON's IOM has the size-by-size list. Codes N and Q (DX air handler refrigeration circuits) are left out because the current IOM's layout garbles them.
  • Filters are the standard unit filters (option 0, 2 in. pleated MERV 8) without return-air bypass. Return-air bypass, 4 in. racks, pre-filters and energy recovery change the count and size. 11 and 13-ton units are left blank because AAON lists them under both the B and C cabinet tables; count the rack.
  • AAON does not publish a serial-number date format in the IOM, so there is no serial decoder.