Lennox · model number decoder

Lennox Landmark

Lennox's standard and high-efficiency R-410A packaged rooftop line (KG gas/electric, KC electric/electric, KH heat pump). The 12-character model tells you unit type, generation, size, efficiency, blower, heat and voltage.

Gas/electric, electric/electric and heat pump packaged rooftop · 2–12.5 tons · R-410A

Decoded against Lennox’s published nomenclature. Characters we can’t match are flagged, not guessed. What you type stays in this tab.

Sizes and filter sizes

Size codeNominal tonsReturn-air filters, KGB gas/electric (2nd gen)Return-air filters, KCB electric/electric (2nd gen)Return-air filters, KHB heat pump (2nd gen)Return-air filters, KGA gas/electric (1st gen)Return-air filters, KCA electric/electric (1st gen)Return-air filters, KHA heat pump (1st gen)Return-air filters, KGA/KGB gas/electricReturn-air filters, KCA/KCB electric/electric
0242(4) 16 x 20 x 2 in.(4) 16 x 20 x 2 in.(4) 16 x 20 x 2 in.—————
0302.5(4) 16 x 20 x 2 in.(4) 16 x 20 x 2 in.(4) 16 x 20 x 2 in.—————
0363(4) 16 x 20 x 2 in.(4) 16 x 20 x 2 in.(4) 16 x 20 x 2 in.(4) 16 x 20 x 2 in.(4) 16 x 20 x 2 in.(4) 16 x 20 x 2 in.——
0484(4) 16 x 20 x 2 in.(4) 16 x 20 x 2 in.(4) 20 x 20 x 2 in.(4) 16 x 20 x 2 in.(4) 16 x 20 x 2 in.(4) 16 x 20 x 2 in.——
0605(4) 20 x 20 x 2 in.(4) 20 x 20 x 2 in.(4) 20 x 20 x 2 in.(4) 16 x 20 x 2 in.(4) 16 x 20 x 2 in.(4) 20 x 20 x 2 in.——
0726(4) 20 x 20 x 2 in.(4) 20 x 20 x 2 in.—(4) 20 x 20 x 2 in.(4) 20 x 20 x 2 in.(4) 20 x 20 x 2 in.——
0746(4) 20 x 20 x 2 in.(4) 20 x 20 x 2 in.(4) 20 x 20 x 2 in.—————
0907.5(4) 20 x 20 x 2 in.(4) 20 x 20 x 2 in.—(4) 20 x 20 x 2 in.(4) 20 x 20 x 2 in.———
0927.5——————(4) 20 x 25 x 2 in.(4) 20 x 25 x 2 in.
1028.5——————(4) 20 x 25 x 2 in.(4) 20 x 25 x 2 in.
12010——————(4) 20 x 25 x 2 in.(4) 20 x 25 x 2 in.
15012.5——————(4) 20 x 25 x 2 in.(4) 20 x 25 x 2 in.

Source: Bulletin No. 210786, pages 1, 17, 18, 19, 21, 23; Bulletin No. 210822, pages 1, 17, 18, 19, 20; Bulletin No. 210789, pages 15, 16, 18, 20; Bulletin No. 210779, pages 14, 15; Bulletin No. 210785, pages 13, 14; Bulletin No. 210788, pages 12, 13; Bulletin No. 210778, pages 12, 13; Bulletin No. 210821, pages 17, 18, 19, 20. Factory filter sizes. Check the rack before ordering; filters get changed over the years.

Lennox Landmark model number nomenclature

Example: KGB060S4BS1Y. Select a position to jump to its codes.

Position 1 Brand/family

KLandmark

Bulletin No. 210822, page 1

Position 2 Unit type

GGas heat with electric cooling
CElectric cooling with optional electric heat
HHeat pump

Bulletin No. 210786, page 1; Bulletin No. 210789, page 1; Bulletin No. 210779, page 1

Position 3 Major design sequence

A1st generation
B2nd generation

Bulletin No. 210822, page 1

Position 4–6 Nominal cooling capacity

0242 tons
0302.5 tons
0363 tons
0484 tons
0605 tons
0726 tons
0746 tons
0907.5 tons
0927.5 tons
1028.5 tons
12010 tons
15012.5 tons

Bulletin No. 210786, page 1; Bulletin No. 210822, page 1

Position 7 Cooling efficiency

HHigh efficiency
SStandard efficiency

Bulletin No. 210786, page 1

Position 8 Refrigerant

4R-410A

Bulletin No. 210786, page 1

Position 9 Blower type

DDirect drive blower (KGB lists it as PSC)
EDirect drive blower, ECM motor
BBelt drive blower, constant air volume
TBelt drive blower, two speed
MBelt drive blower, MSAV multi-stage air volume (7.5–12.5 tons)

Bulletin No. 210786, page 1; Bulletin No. 210822, page 1

Position 10 Heating type (gas) or factory electric heat

SStandard gas heat, 1 stage (sizes 024–090)
SStandard gas heat, 2 stage (sizes 092–150)
MMedium gas heat, 1 stage (sizes 024–090)
MMedium gas heat, 2 stage (sizes 092–150)
UMedium gas heat, 2 stage
THigh gas heat, 1 stage
HHigh gas heat, 2 stage
WStandard gas heat, 1 stage, low NOx
BStandard gas heat, 2 stage, low NOx
YMedium gas heat, 1 stage, low NOx
QMedium gas heat, 2 stage, low NOx
ZHigh gas heat, 1 stage, low NOx
XHigh gas heat, 2 stage, low NOx
NNo factory-installed heat (electric/electric and heat pump units)
C7.5 kW factory electric heat (KCA/KCB 7.5–12.5 tons)
E15 kW factory electric heat (KCA/KCB 7.5–12.5 tons)
G22.5 kW factory electric heat (KCA/KCB 7.5–12.5 tons)
J30 kW factory electric heat (KCA/KCB 7.5–12.5 tons)
K45 kW factory electric heat (KCA/KCB 7.5–12.5 tons)
L60 kW factory electric heat (KCA/KCB 7.5–12.5 tons)

Bulletin No. 210786, page 1; Bulletin No. 210822, page 1; Bulletin No. 210789, page 1; Bulletin No. 210821, page 1

Position 11 Minor design sequence

11st revision
22nd revision
33rd revision

Bulletin No. 210786, page 1

Position 12 Voltage

P208/230 V, single phase, 60 Hz (2–7.5 ton cabinets)
Y208/230 V, three phase, 60 Hz
G460 V, three phase, 60 Hz
J575 V, three phase, 60 Hz

Bulletin No. 210789, page 1; Bulletin No. 210786, page 1

What this page doesn’t cover

  • Covers the Landmark R-410A 60 Hz line: 2–7.5 ton KGB/KCB/KHB (2nd generation) and KGA/KCA/KHA (1st generation) cabinets, plus 7.5–12.5 ton KGA/KGB and KCA/KCB. Lennox now sells this cabinet family as Xion (KGC and later); those are not decoded here.
  • Heat codes S and M mean 1-stage gas heat on 2–7.5 ton units (sizes 024–090) and 2-stage gas heat on 7.5–12.5 ton units (sizes 092–150). Read the size code before the heat code.
  • Position 10 is gas heat on KG units and factory electric heat on KC/KH units. On the 2–7.5 ton KC and KH units Lennox lists only N (no factory heat); electric heat there is a separate accessory.
  • Return-air filters vary by generation and unit type at the same size (for example a 5-ton 1st-generation KGA uses 16 x 20 filters where a 2nd-generation KGB uses 20 x 20). Match the third character (A or B) and unit type, then confirm against the rack in the unit.
  • KHA heat pumps in 7.5–12.5 tons are not covered: no Lennox-hosted 60 Hz specification sheet was found. 50 Hz units and dual-fuel KDB units are also out of scope.
  • No serial-number date decoder: no Lennox-owned document found states the commercial rooftop serial format.

Decoded it on the roof?
Keep it with the unit.

BoltWright keeps every rooftop’s model, serial, history and open findings with the building, so the next tech starts with what the last one knew. Capture works without reception.

Start a free service report

See BoltWright →

Independent BoltWright reference, not a manufacturer service manual. Lennox is named to identify the equipment; no endorsement is implied. Confirm against the unit’s nameplate and Lennox’s current literature before ordering parts.