Rheem · model number decoder

Rheem Renaissance RGEC / RGED gas/electric

Rheem's current Renaissance Line gas/electric rooftops: RGEC (3–6 tons) and RGED (7.5–12.5 tons) on R-454B. The 20-character model tells you cabinet, efficiency, tonnage, voltage, fan drive, heat size, controls and factory options.

Gas heat / electric cooling packaged rooftop · 3–12.5 tons · R-454B

Decoded against Rheem’s published nomenclature. Characters we can’t match are flagged, not guessed. What you type stays in this tab.

Sizes and filter sizes

Size codeNominal tonsReturn-air filters
0363(4) 16 x 16 x 2 in.
0484(4) 16 x 16 x 2 in.
0605(4) 16 x 16 x 2 in.
0726(4) 16 x 16 x 2 in.
0907.5(4) 20 x 20 x 2 in.
1028.5(4) 20 x 20 x 2 in.
12010(4) 20 x 25 x 2 in.
15012.5(4) 20 x 25 x 2 in.

Source: R11-880, pages 12, 15, 16, 17, 18; R11-881, pages 13, 16. Factory filter sizes. Check the rack before ordering; filters get changed over the years.

Rheem Renaissance RGEC / RGED gas/electric model number nomenclature

Example: RGEDYB090ACF152AAEF3. Select a position to jump to its codes.

Position 1 Brand

RRheem

R11-881, page 13

Position 2–3 Unit type

GEPackaged gas/electric

R11-881, page 13

Position 4 Cabinet

CSmall commercial cabinet (RGEC, 3–6 tons)
DMedium commercial cabinet (RGED, 7.5–12.5 tons)

R11-880, page 12; R11-881, page 13

Position 5 Refrigerant

YR-454B

R11-881, page 13

Position 6 Efficiency level

BStandard efficiency (Classic series)
CHigh efficiency (Classic Plus, RGECYC, 3–5 tons only)

R11-881, page 13; R11-880, page 12

Position 7–9 Nominal cooling size

0363 tons
0484 tons
0605 tons
0726 tons (standard efficiency only)
0907.5 tons
1028.5 tons
12010 tons
15012.5 tons

R11-880, page 12; R11-881, page 13

Position 10 Major series

A1st design

R11-881, page 13

Position 11 Voltage

J208-230 V, single phase (RGEC only; not on 6-ton models)
C208-230 V, 3 phase
D460 V, 3 phase
Y575 V, 3 phase (not on reheat models or high-efficiency RGECYC)

R11-880, page 12; R11-881, page 13

Position 12 Indoor fan drive

TDirect drive constant-torque motor, standard static (RGEC)
UDirect drive constant-torque motor, high static (RGEC; not with J voltage)
FBelt drive with VFD, low static (RGED)
GBelt drive with VFD, medium static (RGED)
HBelt drive with VFD, high static (RGED 7.5–10 tons only)

R11-880, page 12; R11-881, page 13

Position 13–14 Gas heat size

0775,000 Btu/h (RGEC)
10100,000 Btu/h (RGEC)
12Largest RGEC heat: the model key says 125,000 Btu/h; the heating table lists 120,000 Btu/h input
15150,000 Btu/h (RGED)
20205,000 Btu/h (RGED 7.5 tons only)
22225,000 Btu/h (RGED)

R11-880, page 12; R11-881, page 13

Position 15 Heat configuration

2Two-stage gas heat
BTwo-stage gas heat, stainless steel heat exchanger

R11-881, page 13

Position 16 Controls

ACoreCommand, non-communicating
BCoreCommand with Comfort Alert diagnostics
CClearControl DDC
DClearControl DDC with Comfort Alert diagnostics

R11-881, page 13

Position 17 Minor series

A1st design

R11-881, page 13

Position 18 Factory option 1 (coil protection, access, reheat)

ANone
BLouver (coil) protection
CHinged access panels
DLouver protection and hinged access
ELouver protection and coil coating
FLouver protection, hinged access and coil coating
NHumidiDry hot gas reheat (RGED: ClearControl units only)
PLouver protection and HumidiDry reheat
QHumidiDry reheat and hinged access
RLouver protection, HumidiDry reheat and coil coating
SLouver protection, HumidiDry reheat and hinged access
TLouver protection, HumidiDry reheat, hinged access and coil coating

R11-881, page 14

Position 19 Factory option 2 (low ambient, outlet, disconnect)

ANone
BLow ambient and freeze stat
CNon-powered convenience outlet
DLow ambient/freeze stat and non-powered outlet
EDisconnect switch
FLow ambient/freeze stat and disconnect switch
HNon-powered outlet and disconnect switch
KLow ambient/freeze stat, non-powered outlet and disconnect switch

R11-881, page 14

Position 20 Factory option 3 (economizer, smoke detectors)

0None
1Downflow economizer
2Return smoke detector
3Economizer and return smoke detector
4Supply and return smoke detectors
5Economizer with supply and return smoke detectors

R11-881, page 14

What this page doesn’t cover

  • Covers the current R-454B Renaissance RGEC and RGED units. The R-410A Renaissance units (RGEDZR, RGEDZS, RGEDZT and similar) and the older RKNL units use different codes and are not decoded here.
  • The 15–25 ton RGEG uses a four-character option code and different control codes, so it is not decoded here.
  • Positions 18–20 are the factory option code; Rheem prints AA0 when no options were ordered. Positions 18–20 mean the same thing on RGEC and RGED.
  • Two places where Rheem's documents disagree: the RGEC model key lists heat code 12 as 125,000 Btu/h while its heating table shows 120,000 Btu/h input, and the RGED model key limits 225,000 Btu/h heat to 7.5–10 tons while its heating table lists it on 8.5–12.5 tons. Trust the rating plate.
  • Filter sizes are the factory return-air filters from the general data tables. Confirm against the rack in the unit; a previous contractor may have changed the filter arrangement.
  • No serial-number date decoder: Rheem does not publish the serial format in these documents or on rheem.com. Use the manufacture date on the rating plate.