York (Johnson Controls) · model number decoder
York ZF, ZJ and ZR Series 20 (15–25 ton)
York's 15–25 ton Series 20 rooftops: ZF (Sunline, standard efficiency), ZJ (Sunline Magnum, high efficiency) and ZR (MagnaDRY reheat), sizes 180, 210, 240 and 300. The 18-character model tells you tonnage, gas heat size, blower, voltage, economizer, controls, cabinet and generation.
Gas heat / electric cooling packaged rooftop, with cooling-only and reheat versions · 15–25 tons · R-410A
Model numbers starting ZF180, ZF210, ZF240, ZF300, ZJ180, ZJ210, ZJ240, ZJ300, ZR180, ZR240 or ZR300.
Quick answers
- Tonnage from the model number
ZF240N30B4A1AAA1A2is a 20-ton unit: characters 3–5,240, are the nominal size.180= 15 tons210= 17.5 tons240= 20 tons300= 25 tonsSource: 5168277-YTG-K-0119, page 4.
- Factory filters by tonnage
15 tons (12) 12 x 24 x 2 in. ZJ filters (2 in. standard)(2) 20 x 24 x 4 in. and (4) 24 x 24 x 4 in. ZJ filters (4 in. option)(4) 16 x 25 x 2 in. and (4) 16 x 20 x 2 in. ZR filters (2 in. standard)(4) 16 x 25 x 4 in. and (4) 16 x 20 x 4 in. ZR filters (4 in. option)(5) 18 x 24 x 2 in. ZF filters (2 in. standard)(5) 18 x 24 x 4 in. ZF filters (4 in. option) 17.5 tons (12) 12 x 24 x 2 in. ZJ filters (2 in. standard), ZF filters (2 in. standard)(2) 20 x 24 x 4 in. and (4) 24 x 24 x 4 in. ZJ filters (4 in. option), ZF filters (4 in. option) 20 tons (12) 12 x 24 x 2 in. ZJ filters (2 in. standard)(2) 20 x 24 x 4 in. and (4) 24 x 24 x 4 in. ZJ filters (4 in. option)(4) 16 x 25 x 2 in. and (4) 16 x 20 x 2 in. ZR filters (2 in. standard), ZF filters (2 in. standard)(4) 16 x 25 x 4 in. and (4) 16 x 20 x 4 in. ZR filters (4 in. option), ZF filters (4 in. option) 25 tons (12) 12 x 24 x 2 in. ZJ filters (2 in. standard), ZF filters (2 in. standard)(2) 20 x 24 x 4 in. and (4) 24 x 24 x 4 in. ZJ filters (4 in. option), ZF filters (4 in. option)(4) 16 x 25 x 2 in. and (4) 16 x 20 x 2 in. ZR filters (2 in. standard)(4) 16 x 25 x 4 in. and (4) 16 x 20 x 4 in. ZR filters (4 in. option) Source: 5168277-YTG-K-0119, pages 15, 17, 19. Check the rack before ordering; filters get changed over the years.
- Age from the serial number
We haven’t found a York (Johnson Controls) document that explains how to date this family’s serial number, so we don’t decode it. Other ways to tell a rooftop unit’s age
Sizes and filter sizes
| Size code | Nominal tons | ZJ filters (2 in. standard) | ZJ filters (4 in. option) | ZR filters (2 in. standard) | ZR filters (4 in. option) | ZF filters (2 in. standard) | ZF filters (4 in. option) |
|---|---|---|---|---|---|---|---|
| 180 | 15 | (12) 12 x 24 x 2 in. | (2) 20 x 24 x 4 in. and (4) 24 x 24 x 4 in. | (4) 16 x 25 x 2 in. and (4) 16 x 20 x 2 in. | (4) 16 x 25 x 4 in. and (4) 16 x 20 x 4 in. | (5) 18 x 24 x 2 in. | (5) 18 x 24 x 4 in. |
| 210 | 17.5 | (12) 12 x 24 x 2 in. | (2) 20 x 24 x 4 in. and (4) 24 x 24 x 4 in. | — | — | (12) 12 x 24 x 2 in. | (2) 20 x 24 x 4 in. and (4) 24 x 24 x 4 in. |
| 240 | 20 | (12) 12 x 24 x 2 in. | (2) 20 x 24 x 4 in. and (4) 24 x 24 x 4 in. | (4) 16 x 25 x 2 in. and (4) 16 x 20 x 2 in. | (4) 16 x 25 x 4 in. and (4) 16 x 20 x 4 in. | (4) 16 x 25 x 2 in. and (4) 16 x 20 x 2 in. | (4) 16 x 25 x 4 in. and (4) 16 x 20 x 4 in. |
| 300 | 25 | (12) 12 x 24 x 2 in. | (2) 20 x 24 x 4 in. and (4) 24 x 24 x 4 in. | (4) 16 x 25 x 2 in. and (4) 16 x 20 x 2 in. | (4) 16 x 25 x 4 in. and (4) 16 x 20 x 4 in. | (12) 12 x 24 x 2 in. | (2) 20 x 24 x 4 in. and (4) 24 x 24 x 4 in. |
Source: 5168277-YTG-K-0119, pages 4, 15, 17, 19. Factory filter sizes. Check the rack before ordering; filters get changed over the years.
York ZF, ZJ and ZR Series 20 (15–25 ton) model number nomenclature
Example: ZF240N30B4A1AAA1A2. Select a position to jump to its codes.
Position 1 Product category
| Z | Single-package air conditioner, R-410A |
|---|
5168277-YTG-K-0119, page 4
Position 2 Product identifier
| F | ZF: packaged air conditioner, standard efficiency (Sunline) |
|---|---|
| J | ZJ: packaged air conditioner, high efficiency (Sunline Magnum) |
| R | ZR: packaged air conditioner with reheat (MagnaDRY) |
5168277-YTG-K-0119, page 4
Position 3–5 Nominal cooling capacity
| 180 | 15 tons |
|---|---|
| 210 | 17.5 tons |
| 240 | 20 tons |
| 300 | 25 tons |
5168277-YTG-K-0119, page 4
Position 6–8 Heat type and heat capacity (digit 6 type, digits 7–8 size)
| C00 | Cooling only, no gas heat (electric heat, if any, is field installed) |
|---|---|
| N30 | 2-stage natural gas, aluminized steel heat exchanger, 300 MBH input |
| N40 | 2-stage natural gas, aluminized steel heat exchanger, 400 MBH input |
| N40 | 2-stage natural gas, aluminized steel heat exchanger, 375 MBH input on the ZF180 |
| S30 | 2-stage natural gas, stainless steel heat exchanger, 300 MBH input |
| S40 | 2-stage natural gas, stainless steel heat exchanger, 400 MBH input (375 MBH on the ZF180) |
5168277-YTG-K-0119, page 4
Position 9 Blower option
| B | Standard static |
|---|---|
| C | Low static (size 300 only) |
| D | High static |
| E | VFD/VAV, standard static |
| F | VFD/VAV, low static (size 300 only) |
| G | VFD/VAV, high static |
| H | VFD/VAV with bypass, standard static |
| J | VFD/VAV with bypass, low static (size 300 only) |
| K | VFD/VAV with bypass, high static |
| L | VAV, customer-supplied VFD, standard static |
| M | VAV, customer-supplied VFD, low static (size 300 only) |
| N | VAV, customer-supplied VFD, high static |
| P | IntelliSpeed VFD, standard static |
| Q | IntelliSpeed VFD, low static (size 300 only) |
| R | IntelliSpeed VFD, high static |
| S | IntelliSpeed VFD with bypass, standard static |
| T | IntelliSpeed VFD with bypass, low static (size 300 only) |
| U | IntelliSpeed VFD with bypass, high static |
| V | IntelliSpeed, customer-supplied VFD, standard static |
| W | IntelliSpeed, customer-supplied VFD, low static (size 300 only) |
| X | IntelliSpeed, customer-supplied VFD, high static |
5168277-YTG-K-0119, page 4
Position 10 Voltage
| 2 | 208/230-3-60 |
|---|---|
| 4 | 460-3-60 |
| 5 | 575-3-60 |
5168277-YTG-K-0119, page 4
Position 11 Outdoor air option
| A | No economizer |
|---|---|
| B | Economizer with barometric relief (downflow only) |
| C | Economizer without barometric relief |
| D | Economizer with power exhaust (downflow only) |
| H | Motorized damper |
| J | Motorized damper with barometric relief (downflow only) |
5168277-YTG-K-0119, page 4
Position 12 Service options
| 1 | None |
|---|---|
| 2 | Disconnect switch |
| 3 | Non-powered convenience outlet |
| 4 | Powered convenience outlet |
| 5 | Disconnect switch and non-powered convenience outlet |
| 6 | Disconnect switch and powered convenience outlet |
| 7 | High short-circuit current rating |
| 8 | High short-circuit current rating, disconnect switch |
| 9 | High short-circuit current rating, disconnect switch, non-powered convenience outlet |
5168277-YTG-K-0119, page 4
Position 13 Sensors
| A | None |
|---|---|
| B | Phase monitor |
| C | Dirty filter switch |
| D | Supply-air smoke detector |
| E | Return-air smoke detector |
| F | Phase monitor and dirty filter switch |
| G | Phase monitor and supply-air smoke detector |
| H | Phase monitor and return-air smoke detector |
| J | Dirty filter switch and supply-air smoke detector |
| K | Dirty filter switch and return-air smoke detector |
| L | Supply- and return-air smoke detectors |
| M | Phase monitor, dirty filter switch and supply-air smoke detector |
| N | Phase monitor, dirty filter switch and return-air smoke detector |
| P | Phase monitor and supply- and return-air smoke detectors |
| Q | Dirty filter switch and supply- and return-air smoke detectors |
| R | Phase monitor, dirty filter switch and supply- and return-air smoke detectors |
5168277-YTG-K-0119, page 4
Position 14 Controls option
| A | Stand-alone Smart Equipment control |
|---|---|
| C | Smart Equipment with BACnet MS/TP, Modbus, N2 communication card |
| D | CPC controller, dirty filter switch, air proving switch |
| G | Novar UCM controller, dirty filter switch, air proving switch |
| H | Honeywell Excel 10 controller, dirty filter switch, air proving switch |
| M | Verasys single zone |
| N | Verasys changeover bypass |
| P | Verasys VAV |
5168277-YTG-K-0119, page 4
Position 15 Refrigeration
| A | Standard refrigeration |
|---|---|
| B | E-coated condenser coil |
| C | E-coated evaporator coil |
| D | Hot gas bypass |
| F | E-coated condenser and evaporator coils |
| G | E-coated condenser and evaporator coils, hot gas bypass |
| J | E-coated condenser coil, hot gas bypass |
| M | E-coated evaporator coil, hot gas bypass |
5168277-YTG-K-0119, page 4
Position 16 Additional options (filters, coil guard)
| 1 | Standard 2 in. throwaway filters |
|---|---|
| 2 | 2 in. pleated filters, MERV 8 |
| 3 | 4 in. pleated filters, MERV 13 |
| 4 | Coil guard, standard filters |
| 5 | 2 in. pleated filters, coil guard |
| 6 | 4 in. pleated filters, coil guard |
5168277-YTG-K-0119, page 4
Position 17 Cabinet options
| A | Standard cabinet |
|---|---|
| B | Hinged, toolless filter door |
| C | Hinged, toolless access doors |
| D | Double-wall cabinet with hinged, toolless access doors (ZJ and ZR only) |
| E | Stainless steel drain pan |
| F | Stainless steel drain pan, hinged filter door |
| G | Stainless steel drain pan, hinged access doors |
| H | Stainless steel drain pan, double-wall cabinet with hinged access doors |
| J | Double-wall cabinet |
| K | Double-wall cabinet, hinged filter door |
| L | Double-wall cabinet, stainless steel drain pan |
| M | Double-wall cabinet, stainless steel drain pan, hinged filter door |
5168277-YTG-K-0119, page 4
Position 18 Product generation
| 1 | First generation |
|---|---|
| 2 | Second generation |
5168277-YTG-K-0119, page 4
Notes and limits
- Covers ZF, ZJ and ZR Series 20 units, sizes 180–300 (15–25 tons), in the 18-character model number from York's January 2019 technical guide. The guide lists ZR in sizes 180, 240 and 300 only.
- The 3–12.5 ton ZF, ZJ, ZH and ZR units share the same letters but use their own pages; this page answers only when the model starts with one of the Series 20 sizes listed above.
- Gas heat is 2-stage only. Heat code 40 means 400 MBH input, except on the ZF180, where York lists it as 375 MBH. Electric heat for these units is field installed and does not appear in the model number.
- Filters come from the physical data tables: 2 in. throwaway (MERV 3) as standard, 2 in. pleated MERV 8 in the same sizes as an option, and 4 in. pleated MERV 13 as an option. On the ZJ, and on the ZF210 and ZF300, the 4 in. option uses different filter sizes from the 2 in. rack. Confirm against the rack in the unit.
- No serial-number date decoder: we found no York or Johnson Controls document that states the serial format for these units.