Trane · model number decoder

Trane Precedent YSK/YHK/TSK/THK (R-454B)

Trane's R-454B Precedent rooftop, 3 to 25 tons, in cooling-only (TSK, THK) and gas/electric (YSK, YHK) versions. The K in the third digit marks R-454B; the model number also gives efficiency, tonnage, voltage, heat and factory options.

Packaged rooftop, cooling only or gas/electric · 3–25 tons · R-454B

Model numbers starting TSK, THK, YSK or YHK.

Decoded against Trane’s published nomenclature. If a character doesn’t match, we flag it instead of guessing. What you type stays in this tab.

Quick answers

Tonnage from the model number

YHK090A3S0M**D0B0010100A10000 is a 7.5-ton unit: characters 4–6, 090, are the nominal size.

036 = 3 tons 048 = 4 tons 060 = 5 tons 072 = 6 tons 090 = 7.5 tons 102 = 8.5 tons 120 = 10 tons 150 = 12.5 tons 180 = 15 tons 210 = 17.5 tons 240 = 20 tons 300 = 25 tons

Source: RT-PRC115F-EN, page 23.

Factory filters by tonnage
3 tons(4) 20 x 20 x 2 in.
4–5 tons(4) 20 x 20 x 2 in. TSK, YSK(2) 18 x 24 x 2 in. and (3) 24 x 16 x 2 in. THK, YHK
6–10 tons(2) 18 x 24 x 2 in. and (3) 24 x 16 x 2 in.
12.5 tons(3) 18 x 18 x 2 in. and (3) 24 x 18 x 2 in. TSK(2) 18 x 24 x 2 in. and (3) 24 x 16 x 2 in. YSK(8) 20 x 24 x 2 in. THK, YHK
15–25 tons(8) 20 x 24 x 2 in.

Source: RT-PRC115F-EN, pages 26, 29, 33, 37. Check the rack before ordering; filters get changed over the years.

Age from the serial number

The first two digits are the year and the next two the week it was built. 150500273D was built in week 5 of 2015. How to read it

Source: Trane Support article 44514808922893.

Sizes and filter sizes

Size codeNominal tonsReturn-air filters (TSK)Return-air filters (YSK)Return-air filters (THK)Return-air filters (YHK)Compressors
0363(4) 20 x 20 x 2 in.(4) 20 x 20 x 2 in.(4) 20 x 20 x 2 in.(4) 20 x 20 x 2 in.1 scroll
0484(4) 20 x 20 x 2 in.(4) 20 x 20 x 2 in.(2) 18 x 24 x 2 in. and (3) 24 x 16 x 2 in.(2) 18 x 24 x 2 in. and (3) 24 x 16 x 2 in.1 scroll
0605(4) 20 x 20 x 2 in.(4) 20 x 20 x 2 in.(2) 18 x 24 x 2 in. and (3) 24 x 16 x 2 in.(2) 18 x 24 x 2 in. and (3) 24 x 16 x 2 in.1 scroll
0726(2) 18 x 24 x 2 in. and (3) 24 x 16 x 2 in.(2) 18 x 24 x 2 in. and (3) 24 x 16 x 2 in.(2) 18 x 24 x 2 in. and (3) 24 x 16 x 2 in.(2) 18 x 24 x 2 in. and (3) 24 x 16 x 2 in.2 manifolded scrolls
0907.5(2) 18 x 24 x 2 in. and (3) 24 x 16 x 2 in.(2) 18 x 24 x 2 in. and (3) 24 x 16 x 2 in.(2) 18 x 24 x 2 in. and (3) 24 x 16 x 2 in.(2) 18 x 24 x 2 in. and (3) 24 x 16 x 2 in.2 manifolded scrolls
1028.5(2) 18 x 24 x 2 in. and (3) 24 x 16 x 2 in.(2) 18 x 24 x 2 in. and (3) 24 x 16 x 2 in.(2) 18 x 24 x 2 in. and (3) 24 x 16 x 2 in.(2) 18 x 24 x 2 in. and (3) 24 x 16 x 2 in.2 manifolded scrolls
12010(2) 18 x 24 x 2 in. and (3) 24 x 16 x 2 in.(2) 18 x 24 x 2 in. and (3) 24 x 16 x 2 in.(2) 18 x 24 x 2 in. and (3) 24 x 16 x 2 in.(2) 18 x 24 x 2 in. and (3) 24 x 16 x 2 in.2 manifolded scrolls
15012.5(3) 18 x 18 x 2 in. and (3) 24 x 18 x 2 in.(2) 18 x 24 x 2 in. and (3) 24 x 16 x 2 in.(8) 20 x 24 x 2 in.(8) 20 x 24 x 2 in.2 manifolded scrolls
18015(8) 20 x 24 x 2 in.(8) 20 x 24 x 2 in.(8) 20 x 24 x 2 in.(8) 20 x 24 x 2 in.2 manifolded scrolls
21017.5(8) 20 x 24 x 2 in.(8) 20 x 24 x 2 in.(8) 20 x 24 x 2 in.(8) 20 x 24 x 2 in.2 manifolded scrolls
24020(8) 20 x 24 x 2 in.(8) 20 x 24 x 2 in.(8) 20 x 24 x 2 in.(8) 20 x 24 x 2 in.2 manifolded scrolls
30025(8) 20 x 24 x 2 in.(8) 20 x 24 x 2 in.(8) 20 x 24 x 2 in.(8) 20 x 24 x 2 in.2 manifolded scrolls

Source: RT-PRC115F-EN, pages 23, 25, 26, 29, 33, 37. Factory filter sizes. Check the rack before ordering; filters get changed over the years.

Trane Precedent YSK/YHK/TSK/THK (R-454B) model number nomenclature

Example: YHK090A3S0M**D0B0010100A10000. Select a position to jump to its codes.

Position 1 Unit function

TCooling only (electric heat optional)
YCooling with gas heat

RT-PRC115F-EN, page 23

Position 2 Cooling efficiency

SStandard efficiency
HHigh efficiency

RT-PRC115F-EN, page 23

Position 3 Refrigerant

KR-454B

RT-PRC115F-EN, page 23

Position 4–6 Nominal cooling size

0363 tons
0484 tons
0605 tons
0726 tons
0907.5 tons
1028.5 tons
12010 tons
15012.5 tons
18015 tons
21017.5 tons
24020 tons
30025 tons

RT-PRC115F-EN, page 23

Position 7 Design sequence

ADesign sequence A (the only sequence in the August 2026 catalog's model tables)

RT-PRC115F-EN, page 185

Position 8 Voltage

3208–230 V, 3 phase, 60 Hz
4460 V, 3 phase, 60 Hz
W575 V, 3 phase, 60 Hz

RT-PRC115F-EN, page 23

Position 9 Unit controls

SSymbio 700 unit controller

RT-PRC115F-EN, page 23

Position 10 Heat type

0Base model (no special heat type)
AGas heat with stainless steel heat exchanger
BModulating gas heat
ESCR modulating electric heat
FHot water coil control (hydronic heat)

RT-PRC115F-EN, page 23

Position 11 Heating capacity (electric on T, gas on Y)

0No heat
B6 kW electric heat
C9 kW electric heat
E12 kW electric heat
G18 kW electric heat
J23 kW electric heat
K27 kW electric heat
N36 kW electric heat
P54 kW electric heat
R72 kW electric heat
LLow gas heat
MMedium gas heat
HHigh gas heat

RT-PRC115F-EN, page 23

Position 12–13 Service sequence

**Factory assigned. Trane does not publish a code list for these two digits.

RT-PRC115F-EN, page 23

Position 14 Fresh air

0No fresh air
AManual outside air damper, 0–50%
BMotorized outside air damper, 0–50%
CEconomizer, dry bulb, without barometric relief
DEconomizer, dry bulb, with barometric relief
EEconomizer, reference enthalpy, without barometric relief
FEconomizer, reference enthalpy, with barometric relief
GEconomizer, comparative enthalpy, without barometric relief
HEconomizer, comparative enthalpy, with barometric relief
KDownflow low-leak economizer, dry bulb, with barometric relief
MDownflow low-leak economizer, reference enthalpy, with barometric relief
PDownflow low-leak economizer, comparative enthalpy, with barometric relief
RDownflow low-leak economizer, differential dry bulb, with barometric relief

RT-PRC115F-EN, page 23

Position 15 Supply fan / motor

0Multi-speed motor
1Optional high static motor
2Single zone VAV, standard motor
3Single zone VAV, oversized/high static motor
4Multiple zone VAV, standard motor
5Multiple zone VAV, oversized/high static motor

RT-PRC115F-EN, page 23

Position 16 Service access / filters

0Standard panels, standard filters
AHinged access panels, standard filters
BStandard panels, 2 in. MERV 8 filters
CHinged access panels, 2 in. MERV 8 filters
DStandard panels, 2 in. MERV 13 filters
EHinged access panels, 2 in. MERV 13 filters

RT-PRC115F-EN, page 23

Position 17 Condenser coil protection

0Standard coil
1CompleteCoat condenser coil

RT-PRC115F-EN, page 23

Position 18 Through-the-base provisions

0None
AThrough-the-base electric
BThrough-the-base gas piping (Y models)
CThrough-the-base electric and gas piping (Y models)

RT-PRC115F-EN, page 23

Position 19 Disconnect / circuit breaker

0None
1Unit-mounted non-fused disconnect
2Unit-mounted circuit breaker

RT-PRC115F-EN, page 23

Position 20 Convenience outlet

0None
AUnpowered 20 A convenience outlet
BPowered 15 A convenience outlet

RT-PRC115F-EN, page 23

Position 21 Communications

0None
1Advanced controller with BACnet interface
3Advanced controller with Air-Fi wireless interface

RT-PRC115F-EN, page 23

Position 22 Refrigeration system

0Standard refrigeration system
AHumidity control (modulating hot gas reheat)

RT-PRC115F-EN, page 23

Position 23 Controls expansion module

0None
1XM-30 expansion module
2XM-32 expansion module
3XM-30 and XM-32 expansion modules
4Two XM-30 expansion modules
5Two XM-32 expansion modules

RT-PRC115F-EN, page 23

Position 24 Smoke detector

0None
AReturn air smoke detector
BSupply air smoke detector
CSupply and return air smoke detectors

RT-PRC115F-EN, page 23

Position 25 System monitoring

0None
1Clogged filter switch
2Condensate overflow switch
3Discharge air sensing tube
4Clogged filter switch and condensate overflow switch
5Clogged filter switch and discharge air sensing tube
6Condensate overflow switch and discharge air sensing tube
7Clogged filter switch, condensate overflow switch and discharge air sensing tube

RT-PRC115F-EN, page 24

Position 26 Not used

*Not used. Trane lists no codes for this digit.

RT-PRC115F-EN, page 24

Position 27 Unit hardware

0No enhancements
1Stainless steel drain pan

RT-PRC115F-EN, page 24

Position 28 Short circuit current rating

0Standard (5 kA) SCCR marking
ATier 2 (65 kA) SCCR marking

RT-PRC115F-EN, page 24

Position 29 Low ambient

0None
ALow ambient cooling to 0°F

RT-PRC115F-EN, page 24

How old is this unit? Reading a Trane serial number

Ten characters on light commercial units built since 2010. Positions 1–2 are the year, 3–4 the week, 5–9 a sequence number and 10 the plant letter: A Monterrey, D Clarksville, L Lynn Haven. Trane’s example 1505 00273 D was built in week 5 of 2015 at Clarksville.

Example: 150500273D

  • Positions 1–2: Year, two digits since 2010 (15 = 2015)
  • Positions 3–4: Week of manufacture
  • Positions 5–9: Sequence number
  • Position 10: Plant: A Monterrey, D Clarksville, L Lynn Haven

Source: Trane Support article 44514808922893. This is the manufacture date, not the install date.

  • Trane shows the position layout and plant letters in a diagram in the article; its text names the fields and lists the year codes. We read the positions from the diagram.
  • Units built 2002–2009 use a one-digit year and earlier units a year letter. Trane lists those codes but doesn’t show where they sit in older serials, so we only date the ten-character format used since 2010.
  • Trane’s year table prints 2019 as “10” and 2025 as “23”. We read both as typing errors: 19 is 2019 and 25 is 2025.

Serial number dates for every rooftop brand we cover →

Notes and limits

  • Covers the R-454B Precedent nomenclature in Trane's August 2026 catalog RT-PRC115F-EN, digits 1–29. Every model table in that catalog shows design sequence A; later sequences may add codes and will show as unknown.
  • One modulating gas heat row in the catalog prints YHK150B**BH where every other row, including other YHK150 rows, shows design sequence A. We treat it as a misprint and list only A.
  • Digits 12–13 are a factory-assigned service sequence with no published code list, and digit 26 is marked not used. Enter them as they appear.
  • THK and YHK are the high-efficiency units, not heat pumps. Precedent heat pumps use separate literature and are not decoded here.
  • Filter sizes are Trane's recommended factory throwaway filters from the general data tables. Where two sizes are listed, the unit takes both sets. Standard and high efficiency units of the same tonnage can take different filters, and at 12.5 tons the TSK150 table lists different filters from the YSK150. Confirm against the rack in the unit.
  • The R-410A Precedent uses C in the third digit (TSC, THC, YSC, YHC) and has its own page. The catalog does not say which R-410A models these units replace.
  • No serial-number date decoder: Trane's catalog does not describe the serial format.

Keep the model and serial with the unit

BoltWright keeps every rooftop’s model, serial, history and open findings with the building, so the next tech starts with what the last one knew. Capture works without reception.

Start a free service report

See BoltWright →

Not the one who picks the software? Send it to whoever runs the shop.

BoltWright put this page together from the manufacturer’s published documents, and we aren’t affiliated with Trane. Check the unit’s nameplate and the current Trane literature before you order parts.

← All rooftop families