York (Johnson Controls) · model number decoder

York Predator ZF (Sun Pro)

York's standard-efficiency ZF gas/electric rooftop, sold as Predator and, from 2020, as Sun Pro. The 18-character model tells you tonnage, heat type and size, blower, voltage, economizer, controls and generation.

Gas heat / electric cooling packaged rooftop · 6.5–12.5 tons · R-410A

Decoded against York (Johnson Controls)’s published nomenclature. Characters we can’t match are flagged, not guessed. What you type stays in this tab.

Sizes and filter sizes

Size codeNominal tonsReturn-air filters (standard 2 in.)Return-air filters (optional 4 in.)Compressors
0786.5(4) 24 x 16 x 2 in.(4) 24 x 16 x 4 in.2 scroll, independent circuits, 50% / 100% capacity steps
0907.5(4) 24 x 16 x 2 in.(4) 24 x 16 x 4 in.2 scroll, independent circuits, 50% / 100% capacity steps
1028.5(4) 24 x 20 x 2 in.(4) 24 x 20 x 4 in.2 scroll, independent circuits, 50% / 100% capacity steps
12010(4) 24 x 20 x 2 in.(4) 24 x 20 x 4 in.2 scroll, independent circuits, 50% / 100% capacity steps
15012.5(4) 24 x 20 x 2 in.(4) 24 x 20 x 4 in.2 scroll, independent circuits, 50% / 100% capacity steps

Source: 5167798-YTG-O-0120, pages 3, 14, 15. Factory filter sizes. Check the rack before ordering; filters get changed over the years.

York Predator ZF (Sun Pro) model number nomenclature

Example: ZF090N18B2A1AAA1A3. Select a position to jump to its codes.

Position 1 Product category

ZSingle-package air conditioner, R-410A

5167798-YTG-O-0120, page 3

Position 2 Product identifier

FPackaged A/C, standard efficiency (ZF gas/electric)

5167798-YTG-O-0120, page 3

Position 3–5 Nominal cooling capacity

0786.5 tons
0907.5 tons
1028.5 tons
12010 tons
15012.5 tons

5167798-YTG-O-0120, page 3

Position 6–8 Heat type and heat capacity (digit 6 type, digits 7–8 size)

C00Cooling only, no heat
N122-stage natural gas, aluminized steel heat exchanger, 120 MBH input (sizes 078, 090, 102)
N182-stage natural gas, aluminized steel heat exchanger, 180 MBH input (all sizes)
N242-stage natural gas, aluminized steel heat exchanger, 240 MBH input (sizes 120, 150)
S122-stage natural gas, stainless steel heat exchanger, 120 MBH input (sizes 078, 090, 102)
S182-stage natural gas, stainless steel heat exchanger, 180 MBH input (all sizes)
S242-stage natural gas, stainless steel heat exchanger, 240 MBH input (sizes 120, 150)
E09Electric heat, 9 kW (sizes 078, 090, 102)
E18Electric heat, 18 kW (all sizes)
E24Electric heat, 24 kW (all sizes)
E36Electric heat, 36 kW (all sizes)
E54Electric heat, 54 kW (sizes 120, 150)

5167798-YTG-O-0120, page 3

Position 9 Blower option

BStandard static
DHigh static
EVFD/VAV, standard static
GVFD/VAV, high static
HVFD/VAV with bypass, standard static
KVFD/VAV with bypass, high static
LVAV, customer-supplied VFD, standard static
NVAV, customer-supplied VFD, high static
PIntelliSpeed VFD, standard static
RIntelliSpeed VFD, high static
SIntelliSpeed VFD with bypass, standard static
UIntelliSpeed VFD with bypass, high static
VIntelliSpeed, customer-supplied VFD, standard static
XIntelliSpeed, customer-supplied VFD, high static

5167798-YTG-O-0120, page 3

Position 10 Voltage

2208/230-3-60
4460-3-60
5575-3-60

5167798-YTG-O-0120, page 3

Position 11 Outdoor air option

ANo economizer
BEconomizer with barometric relief
DEconomizer with power exhaust
HMotorized damper

5167798-YTG-O-0120, page 3

Position 12 Service options

1None
2Disconnect switch
3Non-powered convenience outlet
4Powered convenience outlet
5Disconnect switch and non-powered convenience outlet
6Disconnect switch and powered convenience outlet

5167798-YTG-O-0120, page 3

Position 13 Sensors

ANone
BPhase monitor
CDirty filter switch
DSupply-air smoke detector
EReturn-air smoke detector
FPhase monitor and dirty filter switch
GPhase monitor and supply-air smoke detector
HPhase monitor and return-air smoke detector
JDirty filter switch and supply-air smoke detector
KDirty filter switch and return-air smoke detector
LSupply- and return-air smoke detectors
MPhase monitor, dirty filter switch and supply-air smoke detector
NPhase monitor, dirty filter switch and return-air smoke detector
PPhase monitor and supply- and return-air smoke detectors
QDirty filter switch and supply- and return-air smoke detectors
RPhase monitor, dirty filter switch and supply- and return-air smoke detectors

5167798-YTG-O-0120, page 3

Position 14 Controls option

AStand-alone Smart Equipment control
CSmart Equipment with BACnet MS/TP, Modbus, N2 communication card
DCPC controller, dirty filter switch, air proving switch
FFault detection diagnostics
GNovar UCM controller, dirty filter switch, air proving switch
HHoneywell Excel 10 controller, dirty filter switch, air proving switch
MVerasys single zone
NVerasys changeover bypass
PVerasys VAV
QVerasys single zone with fault detection diagnostics
RVerasys changeover bypass with fault detection diagnostics
TVerasys VAV with fault detection diagnostics

5167798-YTG-O-0120, page 3

Position 15 Refrigeration

AStandard refrigeration
BE-coated condenser coil
CE-coated evaporator coil
DHot gas bypass
FE-coated condenser and evaporator coils
GE-coated condenser and evaporator coils, hot gas bypass
JE-coated condenser coil, hot gas bypass
ME-coated evaporator coil, hot gas bypass

5167798-YTG-O-0120, page 3

Position 16 Additional options (filters, coil guard)

1Standard 2 in. throwaway filters
22 in. pleated filters, MERV 8
34 in. pleated filters, MERV 13
4Coil guard, standard filters
52 in. pleated filters, coil guard
64 in. pleated filters, coil guard

5167798-YTG-O-0120, page 3

Position 17 Cabinet options

AStandard cabinet
EStainless steel drain pan
RReverse drain pan

5167798-YTG-O-0120, page 3

Position 18 Product generation

1First generation
2Second generation
3Third generation

5167798-YTG-O-0120, page 3

What this page doesn’t cover

  • Covers the ZF gas/electric line, sizes 078–150 (6.5–12.5 tons), in the 18-character nomenclature for product generations 1–3. The cited 2020 revision carries the Sun Pro name; earlier revisions of the same document number (5167798-YTG) were published under the Predator name.
  • ZH (heat pump), ZJ (high efficiency) and ZR (reheat/cooling) models, the 3–5 ton sizes and the 15–25 ton ZF/ZJ/ZR Series 20 units use other York documents and are not decoded here yet.
  • Older Predator ZF units (for example York's 2014 'Seventh Generation' technical guide) use a different 19-character model number. If the heat code reads N10, N15, N20, S10, S15 or S20 (heat output in MBH), you are looking at that older format: this decoder does not cover it and the positions after the heat code will not line up.
  • The heat type (digit 6) and heat size (digits 7–8) are decoded together because the same size code means gas input for N/S and kilowatts for E. York's sample model on the nomenclature page shows A in the blower position, which its blower table does not list; the example here uses B (standard static).
  • Filter sizes are the factory filters from the physical data table: 2 in. throwaway (MERV 3) as standard, with 2 in. pleated MERV 8 in the same size, or 4 in. pleated MERV 13 as options. Confirm against the rack in the unit.
  • No serial-number date decoder: we found no York or Johnson Controls document that states the serial format for these units.

Decoded it on the roof?
Keep it with the unit.

BoltWright keeps every rooftop’s model, serial, history and open findings with the building, so the next tech starts with what the last one knew. Capture works without reception.

Start a free service report

See BoltWright →

Independent BoltWright reference, not a manufacturer service manual. York (Johnson Controls) is named to identify the equipment; no endorsement is implied. Confirm against the unit’s nameplate and York (Johnson Controls)’s current literature before ordering parts.

← All rooftop families