Carrier · model number decoder

Carrier WeatherMaker 50TC

Carrier's standard-efficiency WeatherMaker cooling-only rooftop, 3 to 15 tons, with R-410A. The 18-character model tells you cooling staging, tonnage, fan, coils, controls, economizer and voltage.

Electric cooling packaged rooftop, optional field-installed electric heat · 3–15 tons · R-410A

Decoded against Carrier’s published nomenclature. Characters we can’t match are flagged, not guessed. What you type stays in this tab.

Sizes and filter sizes

Size codeNominal tonsReturn-air filters
043(2) 16 x 25 x 2 in.
054(2) 16 x 25 x 2 in.
065(2) 16 x 25 x 2 in.
076(4) 16 x 16 x 2 in.
087.5(4) 16 x 20 x 2 in.
098.5(4) 20 x 20 x 2 in.
1210(4) 20 x 20 x 2 in.
1412.5(4) 20 x 20 x 2 in.
1615(6) 18 x 24 x 2 in.

Source: 50TC-19PD, pages 4, 12; 50TC-7-16-03PD, pages 3, 6, 7, 8. Factory filter sizes. Check the rack before ordering; filters get changed over the years.

Carrier WeatherMaker 50TC model number nomenclature

Example: 50TC-D08A1A5-0A0G0. Select a position to jump to its codes.

Position 13 is always “-” (design revision). The decoder works with or without it.

Position 1–2 Unit heat type

50Electric heat packaged rooftop (cooling only as shipped)

50TC-7-16-03PD, page 3

Position 3–4 Model series

TCWeatherMaker, standard efficiency

50TC-7-16-03PD, page 3

Position 5 Heat size

-No factory heat

50TC-7-16-03PD, page 3

Position 6 Refrigeration system

AOne-stage cooling
BOne-stage cooling with Humidi-MiZer (sizes 04–07)
DTwo-stage cooling (sizes 08–16)
ETwo-stage cooling with Al/Cu condenser coils and Humidi-MiZer (sizes 08–16)
MSingle circuit, two-stage cooling (sizes 08, 09 and 12 only)

50TC-19PD, page 4; 50TC-7-16-03PD, page 3

Position 7–8 Nominal cooling size

043 tons
054 tons
065 tons
076 tons
087.5 tons
098.5 tons
1210 tons
1412.5 tons
1615 tons

50TC-19PD, page 4; 50TC-7-16-03PD, page 3

Position 9 Sensor options

ANone
BReturn-air smoke detector
CSupply-air smoke detector
DReturn- and supply-air smoke detectors
ECO₂ sensor
FReturn-air smoke detector and CO₂ sensor
GSupply-air smoke detector and CO₂ sensor
HReturn- and supply-air smoke detectors and CO₂ sensor
JCondensate overflow switch
KCondensate overflow switch and return-air smoke detector
LCondensate overflow switch and return- and supply-air smoke detectors

50TC-7-16-03PD, page 3

Position 10 Indoor fan

1Belt drive, standard static
2Belt drive, medium static
3Belt drive, high static (not on 50TC*M08)
CHigh static with high-efficiency motor (size 16 only)

50TC-7-16-03PD, page 3

Position 11 Coil options (outdoor – indoor – hail guard)

ARTPF Al/Cu – Al/Cu
BRTPF precoat Al/Cu – Al/Cu
CRTPF e-coat Al/Cu – Al/Cu
DRTPF e-coat Al/Cu – e-coat Al/Cu
ERTPF Cu/Cu – Al/Cu
FRTPF Cu/Cu – Cu/Cu
MRTPF Al/Cu – Al/Cu, louvered hail guard
NRTPF precoat Al/Cu – Al/Cu, louvered hail guard
PRTPF e-coat Al/Cu – Al/Cu, louvered hail guard
QRTPF e-coat Al/Cu – e-coat Al/Cu, louvered hail guard
RRTPF Cu/Cu – Al/Cu, louvered hail guard
SRTPF Cu/Cu – Cu/Cu, louvered hail guard
GNovation Al/Al – Al/Cu
HNovation Al/Al – Cu/Cu
JNovation Al/Al – e-coat Al/Cu
KNovation e-coat Al/Al – Al/Cu
LNovation e-coat Al/Al – e-coat Al/Cu
TNovation Al/Al – Al/Cu, louvered hail guard
UNovation Al/Al – Cu/Cu, louvered hail guard
VNovation Al/Al – e-coat Al/Cu, louvered hail guard
WNovation e-coat Al/Al – Al/Cu, louvered hail guard
XNovation e-coat Al/Al – e-coat Al/Cu, louvered hail guard

50TC-7-16-03PD, page 3

Position 12 Voltage

1575-3-60
3208/230-1-60, single phase (sizes 04–06)
5208/230-3-60
6460-3-60

50TC-7-16-03PD, page 3; 50TC-19PD, page 4

Position 14 Base unit controls

0Electromechanical controls (W7212 EconoMi$er IV compatible)
1PremierLink controller
2RTU Open multi-protocol controller
6Electromechanical with 2-speed fan and W7220 economizer controller

50TC-7-16-03PD, page 3

Position 15 Intake / exhaust

ANone
BTemperature economizer with barometric relief
FEnthalpy economizer with barometric relief
K2-position damper
UTemperature ultra-low-leak economizer with barometric relief
WEnthalpy ultra-low-leak economizer with barometric relief

50TC-7-16-03PD, page 3

Position 16 Service options

0None
1Unpowered convenience outlet
2Powered convenience outlet
3Hinged panels
4Hinged panels and unpowered convenience outlet
5Hinged panels and powered convenience outlet

50TC-7-16-03PD, page 3

Position 17 Electrical options

ANone (non-USA models, no SAV)
CNon-fused disconnect (non-USA models, no SAV)
DThru-the-base connections (non-USA models, no SAV)
FNon-fused disconnect and thru-the-base connections (non-USA models, no SAV)
G2-speed indoor fan (VFD) controller
J2-speed fan controller (VFD) and non-fused disconnect
K2-speed fan controller (VFD) and thru-the-base connections
M2-speed fan controller (VFD), non-fused disconnect and thru-the-base connections

50TC-7-16-03PD, page 3

Position 18 Packaging and seismic

0Standard
1LTL
3California seismic compliant label (2012 document)
4LTL and California seismic compliant label (2012 document)

50TC-7-16-03PD, page 3; 50TC-19PD, page 4

How old is it? Reading a Carrier serial number

Ten characters. Positions 1–2 are the week of manufacture on Carrier's fiscal calendar, 3–4 the year, 5 a manufacturing-location letter and 6–10 a sequence number. Carrier's example 3112U12345 was built in week 31 of 2012.

Example: 3112U12345

  • Positions 1–2: Week of manufacture (fiscal calendar)
  • Positions 3–4: Year of manufacture (12 = 2012)
  • Position 5: Manufacturing location
  • Positions 6–10: Sequence number

Source: 50TC-19PD, page 68. This is the manufacture date, not the install date.

What this page doesn’t cover

  • This page covers the R-410A 50TC. Carrier's R-454B (Puron Advance) WeatherMaker rooftops carry different model numbers and are not covered here.
  • Filter sizes are the factory return-air filters from the physical data tables. Confirm against the rack in the unit; a previous contractor may have changed the filter arrangement.
  • Sizes 04–06 (3–5 tons), single-phase voltage code 3 and seismic packaging codes 3 and 4 come from Carrier's 2012 3–15 ton product data. Later 04–06 builds may differ.
  • Size 09 filters changed between documents: the 2012 data lists (4) 16 x 20 x 2 in., the 2021 data (4) 20 x 20 x 2 in. Check the rack.
  • Cooling code A: the 2021 6–15 ton data offers A and B on size 07 only. Older 08, 09 and 12 units can also be A (one stage).
  • Electric heaters are field-installed accessories and are not identified by the model number. Read the heater's own label.
  • The serial format is taken from Carrier's 2012 product data. The week is Carrier's fiscal-calendar week, so the date is approximate.