Trane · model number decoder

Trane Precedent YSC/YHC/TSC/THC

Trane's R-410A Precedent light commercial rooftop in cooling-only (TSC, THC) and gas/electric (YSC, YHC) versions. The model number gives efficiency, tonnage, design sequence, voltage, controls, heat and factory options.

Packaged rooftop, cooling only or gas/electric · 3–10 tons · R-410A

Decoded against Trane’s published nomenclature. Characters we can’t match are flagged, not guessed. What you type stays in this tab.

Sizes and filter sizes

Size codeNominal tonsFilters, standard efficiency (T/YSC)Filters, high efficiency (T/YHC)
0363(2) 20 x 35 x 2 in.(2) 20 x 30 x 2 in.
0373—(2) 20 x 30 x 2 in. (17 Plus)
0474—(4) 16 x 25 x 2 in. (17 Plus)
0484(2) 20 x 35 x 2 in.(4) 16 x 25 x 2 in.
0605(2) 20 x 35 x 2 in.(4) 16 x 25 x 2 in.
0675—(4) 16 x 25 x 2 in. (17 Plus)
0726(4) 16 x 25 x 2 in.(4) 20 x 25 x 2 in.
0746 (dual compressor)—(4) 20 x 25 x 2 in.
0907.5 (single compressor)(4) 16 x 25 x 2 in.—
0927.5 (dual compressor)(4) 20 x 25 x 2 in.(4) 20 x 25 x 2 in.
1028.5(4) 20 x 25 x 2 in.(4) 20 x 25 x 2 in.
12010(4) 20 x 25 x 2 in.(3) 20 x 25 x 2 in. and (2) 20 x 30 x 2 in.

Source: RT-PRC023AY-EN, pages 25, 29, 31, 33, 35, 37; RT-PRC048R-EN, pages 25, 27. Factory filter sizes. Check the rack before ordering; filters get changed over the years.

Trane Precedent YSC/YHC/TSC/THC model number nomenclature

Example: YHC092F4RMA**D0B0000601A1A0. Select a position to jump to its codes.

Position 1 Unit type

TCooling only (electric heat optional)
YCooling with gas heat

RT-PRC023AY-EN, page 25

Position 2 Efficiency

SStandard efficiency
HHigh efficiency

RT-PRC023AY-EN, page 25

Position 3 Airflow

CConvertible (downflow or horizontal)

RT-PRC023AY-EN, page 25

Position 4–6 Nominal cooling size

0363 tons
0373 tons (17 Plus)
0474 tons (17 Plus)
0484 tons
0605 tons
0675 tons (17 Plus)
0726 tons
0746 tons, dual compressor
0907.5 tons, single compressor
0927.5 tons, dual compressor
1028.5 tons
12010 tons

RT-PRC023AY-EN, page 25; RT-PRC048R-EN, page 25

Position 7 Major design sequence

EDesign sequence E (3–6 ton high efficiency, and the 17 Plus 037–067)
FDesign sequence F (4–10 ton high efficiency)
GDesign sequence G (3–5 ton standard efficiency)
HDesign sequence H (6–10 ton standard efficiency)

RT-PRC023AY-EN, pages 29, 31, 33

Position 8 Voltage

1208/230 V, 1 phase, 60 Hz
3208–230 V, 3 phase, 60 Hz
4460 V, 3 phase, 60 Hz
W575 V, 3 phase, 60 Hz

RT-SVX21AD-EN, page 7; RT-PRC023AY-EN, page 25

Position 9 Unit controls

EElectromechanical
RReliaTel microprocessor

RT-PRC023AY-EN, page 25

Position 10 Heat (electric on T, gas on Y)

0No electric heat
A5 kW electric heat, 1 phase
B6 kW electric heat, 3 phase
C9 kW electric heat, 3 phase
D10 kW electric heat, 1 phase
E12 kW electric heat, 3 phase
F14 kW electric heat, 1 phase
G18 kW electric heat
J23 kW electric heat, 3 phase
K27 kW electric heat, 3 phase
N36 kW electric heat, 3 phase
P54 kW electric heat, 3 phase
LLow gas heat
MMedium gas heat
HHigh gas heat
XLow gas heat, stainless steel heat exchanger
YMedium gas heat, stainless steel heat exchanger
ZHigh gas heat, stainless steel heat exchanger

RT-PRC023AY-EN, page 25; RT-SVX21AD-EN, page 7

Position 11 Minor design sequence

AFirst minor design sequence
BSecond minor design sequence

RT-PRC023AY-EN, page 25

Position 12–13 Service sequence

**Factory assigned. Trane does not publish a code list for these two digits.

RT-PRC023AY-EN, page 25

Position 14 Fresh air

0No fresh air
AManual outside air damper, 0–50% (ships loose for field install)
BMotorized outside air damper, 0–50%
CEconomizer, dry bulb, without barometric relief
DEconomizer, dry bulb, with barometric relief
EEconomizer, reference enthalpy, without barometric relief
FEconomizer, reference enthalpy, with barometric relief
GEconomizer, comparative enthalpy, without barometric relief
HEconomizer, comparative enthalpy, with barometric relief
KLow-leak economizer with barometric relief
MLow-leak economizer, reference enthalpy, with barometric relief (the 3–10 ton table prints M the same as K)
PLow-leak economizer, comparative enthalpy, with barometric relief

RT-PRC023AY-EN, page 25; RT-PRC048R-EN, page 25

Position 15 Supply fan / drive

0Standard drive (direct or belt depends on size and efficiency)
1Oversized motor
2Optional belt drive motor
6Single zone VAV
7Multi-speed indoor fan
EVAV supply air temperature control, standard motor

RT-PRC023AY-EN, page 25

Position 16 Service access / filters

0Standard panels, standard filters
AHinged access panels, standard filters
BStandard panels, 2 in. MERV 8 filters
CHinged access panels, 2 in. MERV 8 filters
DStandard panels, 2 in. MERV 13 filters
EHinged access panels, 2 in. MERV 13 filters (the 3–10 ton table prints MERV 8; check the rack)

RT-PRC023AY-EN, page 25; RT-PRC048R-EN, page 25

Position 17 Condenser coil protection

0Standard coil
1Standard coil with hail guard
2Black epoxy pre-coated condenser coil
3Black epoxy pre-coated condenser coil with hail guard
4CompleteCoat condenser coil
5CompleteCoat condenser coil with hail guard

RT-PRC023AY-EN, page 25

Position 18 Through-the-base provisions

0None
AThrough-the-base electric
BThrough-the-base gas piping (Y models)
CThrough-the-base electric and gas piping (Y models)

RT-PRC023AY-EN, page 25

Position 19 Disconnect / circuit breaker

0None
1Unit-mounted non-fused disconnect
2Unit-mounted circuit breaker

RT-PRC023AY-EN, page 25

Position 20 Convenience outlet

0None
AUnpowered convenience outlet
BPowered convenience outlet (3 phase only)

RT-PRC023AY-EN, page 25

Position 21 Communications

0None
1Trane communications interface (TCI)
2LonTalk communications interface
3Novar 2024 controls
4Novar 3051 controls without zone sensor
5Novar 3051 controls interface with DCV
6BACnet communications interface
7Trane Air-Fi wireless communications interface

RT-PRC023AY-EN, page 25

Position 22 Refrigeration system

0Standard refrigeration system (TXV)
BDehumidification (hot gas reheat)

RT-PRC023AY-EN, page 25

Position 23 Refrigeration controls

0None
1Frostat
2Crankcase heater (17 Plus)
3Frostat and crankcase heater (17 Plus)

RT-PRC023AY-EN, page 25; RT-PRC048R-EN, page 25

Position 24 Smoke detector

0None
AReturn air smoke detector
BSupply air smoke detector
CSupply and return air smoke detectors
DPlenum smoke detector

RT-PRC023AY-EN, page 26

Position 25 System monitoring

0None
1Clogged filter switch
2Fan failure switch (the 3–10 ton table prints “fan filter switch”)
3Discharge air sensing tube
4Clogged filter switch and fan failure switch
5Clogged filter switch and discharge air sensing tube
6Fan failure switch and discharge air sensing tube
7Clogged filter switch, fan failure switch and discharge air sensing tube
8Novar return air sensor (Novar 2024)
9Novar zone temperature sensor (Novar 3051)
ACondensate drain pan overflow switch
BClogged filter switch and condensate overflow switch
CFan failure switch and condensate overflow switch
DDischarge air sensing and condensate overflow switch
EClogged filter switch, fan failure switch and condensate overflow switch
FClogged filter switch, discharge air sensing and condensate overflow switch
GFan failure switch, discharge air sensing and condensate overflow switch
HClogged filter, fan failure, discharge air sensing and condensate overflow switches

RT-PRC023AY-EN, page 26

Position 26 Ventilation / diagnostics

0None
ADemand control ventilation (CO₂ wiring; sensor field installed)
BLow-leak economizer with fault detection and diagnostics (FDD)
CFDD with demand control ventilation

RT-PRC023AY-EN, page 26

Position 27 Unit hardware

0No enhancements
1Stainless steel drain pan

RT-PRC023AY-EN, page 26

What this page doesn’t cover

  • Covers the R-410A Precedent T/YSC and T/YHC nomenclature in Trane's December 2022 catalogs (design sequences E, F, G and H). Older design sequences may use different codes and will show as unknown.
  • Digits 12–13 are a factory-assigned service sequence with no published code list. Enter them as they appear; the decoder cannot interpret them.
  • Digits 28 and later (including digit 31, human interface, and digit 34, ultra-low NOx on 17 Plus units) are not decoded.
  • Filter sizes are Trane's recommended factory throwaway filters from the general data tables. Standard and high efficiency units of the same size can take different filters. Confirm against the rack in the unit.
  • Precedent heat pumps (WSC, WHC) use separate literature and are not decoded here.
  • Trane's newer R-454B Precedent (TSK, YSK, THK, YHK, catalog RT-PRC115) and the 6–25 ton YSJ/YHJ units use different model numbers and are not covered by this page.