Carrier · model number decoder

Carrier WeatherMaker 48TC

Carrier's standard-efficiency WeatherMaker gas/electric rooftop, 3 to 15 tons. The 18-character model tells you heat size, cooling staging, tonnage, controls, economizer and voltage.

Gas heat / electric cooling packaged rooftop · 3–15 tons · R-410A

Model numbers starting 48TC.

Decoded against Carrier’s published nomenclature. If a character doesn’t match, we flag it instead of guessing. What you type stays in this tab.

Quick answers

Tonnage from the model number

48TCDD08A1A5-0A0G0 is a 7.5-ton unit: characters 7–8, 08, are the nominal size.

04 = 3 tons 05 = 4 tons 06 = 5 tons 07 = 6 tons 08 = 7.5 tons 09 = 8.5 tons 12 = 10 tons 14 = 12.5 tons 16 = 15 tons

Source: 48TC-19PD, page 4; 48TC-7-16-03PD, page 3.

Factory filters by tonnage
3–5 tons(2) 16 x 25 x 2 in.
6 tons(4) 16 x 16 x 2 in.
7.5 tons(4) 16 x 20 x 2 in.
8.5–12.5 tons(4) 20 x 20 x 2 in.
15 tons(6) 18 x 24 x 2 in.

Source: 48TC-19PD, page 13; 48TC-7-16-03PD, pages 7, 8, 9. Check the rack before ordering; filters get changed over the years.

Age from the serial number

The first four digits are the week and year it was built, on Carrier’s fiscal calendar. 3112U12345 was built in week 31 of 2012. How to read it

Source: 48TC-19PD, page 72.

Sizes and filter sizes

Size codeNominal tonsReturn-air filters
043(2) 16 x 25 x 2 in.
054(2) 16 x 25 x 2 in.
065(2) 16 x 25 x 2 in.
076(4) 16 x 16 x 2 in.
087.5(4) 16 x 20 x 2 in.
098.5(4) 20 x 20 x 2 in.
1210(4) 20 x 20 x 2 in.
1412.5(4) 20 x 20 x 2 in.
1615(6) 18 x 24 x 2 in.

Source: 48TC-19PD, pages 4, 13; 48TC-7-16-03PD, pages 3, 7, 8, 9. Factory filter sizes. Check the rack before ordering; filters get changed over the years.

Carrier WeatherMaker 48TC model number nomenclature

Example: 48TCDD08A1A5-0A0G0. Select a position to jump to its codes.

Position 13 is always “-” (design revision). The decoder works with or without it.

Position 1–2 Unit heat type

48Gas heat packaged rooftop

48TC-7-16-03PD, page 3

Position 3–4 Model series

TCWeatherMaker, standard efficiency

48TC-7-16-03PD, page 3

Position 5 Heat option

DLow heat
EMedium heat
FHigh heat
SLow heat, stainless steel heat exchanger
RMedium heat, stainless steel heat exchanger
THigh heat, stainless steel heat exchanger
LLow NOx, low heat (sizes 04–06)
MLow NOx, medium heat (sizes 04–06)
NLow NOx, high heat (sizes 04–06)

48TC-7-16-03PD, page 3; 48TC-19PD, page 4

Position 6 Refrigeration system

AOne-stage cooling
BOne-stage cooling with Humidi-MiZer (sizes 04–07)
DTwo-stage cooling (sizes 08–16)
ETwo-stage cooling with Al/Cu condenser coils and Humidi-MiZer (sizes 08–16)
MSingle circuit, two-stage cooling (sizes 08, 09 and 12 only)

48TC-19PD, page 4; 48TC-7-16-03PD, page 3

Position 7–8 Nominal cooling size

043 tons
054 tons
065 tons
076 tons
087.5 tons
098.5 tons
1210 tons
1412.5 tons
1615 tons

48TC-19PD, page 4; 48TC-7-16-03PD, page 3

Position 9 Sensor options

ANone
BReturn-air smoke detector
CSupply-air smoke detector
DReturn- and supply-air smoke detectors
ECO₂ sensor
FReturn-air smoke detector and CO₂
GSupply-air smoke detector and CO₂
HReturn- and supply-air smoke detectors and CO₂
JCondensate overflow switch (electromechanical controls only)
KCondensate overflow switch and return-air smoke detector
LCondensate overflow switch and return- and supply-air smoke detectors

48TC-7-16-03PD, page 3

Position 10 Indoor fan

1Belt drive, standard static
2Belt drive, medium static
3Belt drive, high static (not on 48TC*M08)
CHigh static with high-efficiency motor (size 16 only)

48TC-7-16-03PD, page 3

Position 11 Coil options (outdoor – indoor – hail guard)

ARTPF Al/Cu – Al/Cu
BRTPF precoat Al/Cu – Al/Cu
CRTPF e-coat Al/Cu – Al/Cu
DRTPF e-coat Al/Cu – e-coat Al/Cu
ERTPF Cu/Cu – Al/Cu
FRTPF Cu/Cu – Cu/Cu
MRTPF Al/Cu – Al/Cu, louvered hail guard
NRTPF precoat Al/Cu – Al/Cu, louvered hail guard
PRTPF e-coat Al/Cu – Al/Cu, louvered hail guard
QRTPF e-coat Al/Cu – e-coat Al/Cu, louvered hail guard
RRTPF Cu/Cu – Al/Cu, louvered hail guard
SRTPF Cu/Cu – Cu/Cu, louvered hail guard
GNovation Al/Al – Al/Cu
HNovation Al/Al – Cu/Cu
JNovation Al/Al – e-coat Al/Cu
KNovation e-coat Al/Al – Al/Cu
LNovation e-coat Al/Al – e-coat Al/Cu
TNovation Al/Al – Al/Cu, louvered hail guard
UNovation Al/Al – Cu/Cu, louvered hail guard
VNovation Al/Al – e-coat Al/Cu, louvered hail guard
WNovation e-coat Al/Al – Al/Cu, louvered hail guard
XNovation e-coat Al/Al – e-coat Al/Cu, louvered hail guard

48TC-7-16-03PD, page 3

Position 12 Voltage

1575-3-60
3208/230-1-60, single phase (sizes 04–06)
5208/230-3-60
6460-3-60

48TC-7-16-03PD, page 3; 48TC-19PD, page 4

Position 14 Base unit controls

0Electromechanical controls (W7212 EconoMi$er IV compatible)
1PremierLink controller
2RTU Open multi-protocol controller
6Electromechanical with 2-speed fan and W7220 economizer controller

48TC-7-16-03PD, page 3

Position 15 Intake / exhaust

ANone
BTemperature economizer with barometric relief
FEnthalpy economizer with barometric relief
K2-position damper
UTemperature ultra-low-leak economizer with barometric relief
WEnthalpy ultra-low-leak economizer with barometric relief

48TC-7-16-03PD, page 3

Position 16 Service options

0None
1Unpowered convenience outlet
2Powered convenience outlet
3Hinged panels
4Hinged panels and unpowered convenience outlet
5Hinged panels and powered convenience outlet

48TC-7-16-03PD, page 3

Position 17 Electrical options

ANone (non-USA models)
CNon-fused disconnect (non-USA models)
DThru-the-base connections (non-USA models)
FNon-fused disconnect and thru-the-base connections (non-USA models)
G2-speed indoor fan (VFD) controller
J2-speed fan controller (VFD) and non-fused disconnect
K2-speed fan controller (VFD) and thru-the-base connections
M2-speed fan controller (VFD), non-fused disconnect and thru-the-base connections

48TC-7-16-03PD, page 3

Position 18 Packaging and seismic

0Standard
1LTL
3California seismic compliant label (2012 document)
4LTL and California seismic compliant label (2012 document)

48TC-7-16-03PD, page 3; 48TC-19PD, page 4

How old is this unit? Reading a Carrier serial number

Ten characters. Positions 1–2 are the week of manufacture on Carrier's fiscal calendar, 3–4 the year, 5 a manufacturing-location letter and 6–10 a sequence number. Carrier's example 3112U12345 was built in week 31 of 2012.

Example: 3112U12345

  • Positions 1–2: Week of manufacture (fiscal calendar)
  • Positions 3–4: Year of manufacture (12 = 2012)
  • Position 5: Manufacturing location
  • Positions 6–10: Sequence number

Source: 48TC-19PD, page 72. This is the manufacture date, not the install date.

Serial number dates for every rooftop brand we cover →

Notes and limits

  • Filter sizes are the factory return-air filters from the physical data tables. Confirm against the rack in the unit; a previous contractor may have changed the filter arrangement.
  • Sizes 04–06 (3–5 tons), the low-NOx heat codes, single-phase voltage code 3 and seismic packaging codes 3 and 4 come from Carrier's 2012 3–15 ton product data. Later 04–06 builds may differ.
  • Size 09 filters changed between documents: the 2012 data lists (4) 16 x 20 x 2 in., the 2020 data (4) 20 x 20 x 2 in. Check the rack.
  • Cooling code A: the 2020 6–15 ton data offers A and B on size 07 only. Older 08, 09 and 12 units can also be A (one stage).
  • The serial format is taken from Carrier's 2012 product data. The week is Carrier's fiscal-calendar week, so the date is approximate.

Keep the model and serial with the unit

BoltWright keeps every rooftop’s model, serial, history and open findings with the building, so the next tech starts with what the last one knew. Capture works without reception.

Start a free service report

See BoltWright →

Not the one who picks the software? Send it to whoever runs the shop.

BoltWright put this page together from the manufacturer’s published documents, and we aren’t affiliated with Carrier. Check the unit’s nameplate and the current Carrier literature before you order parts.

← All rooftop families