York (Johnson Controls) · model number decoder

York Predator ZH, ZJ and ZR (Sun Pro)

York's ZH, ZJ and ZR packaged rooftops, 3 to 12.5 tons, sold as Sun Pro from 2020 and as Predator before that. They share the 18-character model number with the ZF, so it tells you efficiency line, tonnage, heat type and size, blower, voltage, economizer, controls and generation.

Packaged rooftop: cooling only, gas heat or electric heat, with a reheat version · 3–12.5 tons · R-410A

Model numbers starting ZH, ZJ or ZR.

Decoded against York (Johnson Controls)’s published nomenclature. If a character doesn’t match, we flag it instead of guessing. What you type stays in this tab.

Quick answers

Tonnage from the model number

ZJ090N18B2A1AAA1A2 is a 7.5-ton unit: characters 3–5, 090, are the nominal size.

037 = 3 tons 049 = 4 tons 061 = 5 tons 078 = 6.5 tons 090 = 7.5 tons 102 = 8.5 tons 120 = 10 tons 150 = 12.5 tons

Source: 5167795-YTG-O-0120, page 3.

Factory filters by tonnage
3–5 tons(4) 24 x 16 x 2 in.
6.5–7.5 tons(4) 24 x 16 x 2 in. ZH, ZR(4) 24 x 20 x 2 in. ZJ
8.5–12.5 tons(4) 24 x 20 x 2 in.

Source: 5167795-YTG-O-0120, pages 16, 20, 22, 26, 28, 32. Check the rack before ordering; filters get changed over the years.

Age from the serial number

We haven’t found a York (Johnson Controls) document that explains how to date this family’s serial number, so we don’t decode it. Other ways to tell a rooftop unit’s age

Sizes and filter sizes

Size codeNominal tonsReturn-air filters, ZHReturn-air filters, ZJReturn-air filters, ZR
0373(4) 24 x 16 x 2 in.(4) 24 x 16 x 2 in.(4) 24 x 16 x 2 in.
0494(4) 24 x 16 x 2 in.(4) 24 x 16 x 2 in.(4) 24 x 16 x 2 in.
0615(4) 24 x 16 x 2 in.(4) 24 x 16 x 2 in.(4) 24 x 16 x 2 in.
0786.5(4) 24 x 16 x 2 in.(4) 24 x 20 x 2 in.(4) 24 x 16 x 2 in.
0907.5(4) 24 x 16 x 2 in.(4) 24 x 20 x 2 in.(4) 24 x 16 x 2 in.
1028.5(4) 24 x 20 x 2 in.(4) 24 x 20 x 2 in.(4) 24 x 20 x 2 in.
12010(4) 24 x 20 x 2 in.(4) 24 x 20 x 2 in.(4) 24 x 20 x 2 in.
15012.5(4) 24 x 20 x 2 in.(4) 24 x 20 x 2 in.(4) 24 x 20 x 2 in.

Source: 5167795-YTG-O-0120, pages 3, 16, 20, 22, 26, 28, 32. Factory filter sizes. Check the rack before ordering; filters get changed over the years.

York Predator ZH, ZJ and ZR (Sun Pro) model number nomenclature

Example: ZJ090N18B2A1AAA1A2. Select a position to jump to its codes.

Position 1 Product category

ZSingle-package air conditioner, R-410A

5167795-YTG-O-0120, page 3

Position 2 Product identifier

HZH: standard efficiency at 3–5 tons, high efficiency at 6.5–12.5 tons
JZJ: packaged air conditioner, high efficiency
RZR: standard efficiency with reheat

5167795-YTG-O-0120, page 3

Position 3–5 Nominal cooling capacity

0373 tons
0494 tons
0615 tons
0786.5 tons
0907.5 tons
1028.5 tons
12010 tons
15012.5 tons

5167795-YTG-O-0120, page 3

Position 6–8 Heat type and heat capacity (digit 6 type, digits 7–8 size)

C00Cooling only, no heat
H061-stage natural gas, aluminized steel heat exchanger, 60 MBH input (sizes 037, 049)
H081-stage natural gas, aluminized steel heat exchanger, 80 MBH input (sizes 037, 049, 061)
H121-stage natural gas, aluminized steel heat exchanger, 120 MBH input (sizes 037–102)
H161-stage natural gas, aluminized steel heat exchanger, 160 MBH input (size 061)
J061-stage natural gas, stainless steel heat exchanger, 60 MBH input (sizes 037, 049)
J081-stage natural gas, stainless steel heat exchanger, 80 MBH input (sizes 037, 049, 061)
J121-stage natural gas, stainless steel heat exchanger, 120 MBH input (sizes 037–102)
J161-stage natural gas, stainless steel heat exchanger, 160 MBH input (size 061)
K061-stage low-NOx natural gas, aluminized steel heat exchanger, 60 MBH input (sizes 037, 049)
K081-stage low-NOx natural gas, aluminized steel heat exchanger, 80 MBH input (sizes 037, 049, 061)
K121-stage low-NOx natural gas, aluminized steel heat exchanger, 120 MBH input (sizes 037–102)
K161-stage low-NOx natural gas, aluminized steel heat exchanger, 160 MBH input (size 061)
L061-stage low-NOx natural gas, stainless steel heat exchanger, 60 MBH input (sizes 037, 049)
L081-stage low-NOx natural gas, stainless steel heat exchanger, 80 MBH input (sizes 037, 049, 061)
L121-stage low-NOx natural gas, stainless steel heat exchanger, 120 MBH input (sizes 037–102)
L161-stage low-NOx natural gas, stainless steel heat exchanger, 160 MBH input (size 061)
N062-stage natural gas, aluminized steel heat exchanger, 60 MBH input (sizes 037, 049)
N082-stage natural gas, aluminized steel heat exchanger, 80 MBH input (sizes 037, 049, 061)
N122-stage natural gas, aluminized steel heat exchanger, 120 MBH input (sizes 037–102)
N162-stage natural gas, aluminized steel heat exchanger, 160 MBH input (size 061)
N182-stage natural gas, aluminized steel heat exchanger, 180 MBH input (sizes 078–150)
N242-stage natural gas, aluminized steel heat exchanger, 240 MBH input (sizes 120, 150)
S062-stage natural gas, stainless steel heat exchanger, 60 MBH input (sizes 037, 049)
S082-stage natural gas, stainless steel heat exchanger, 80 MBH input (sizes 037, 049, 061)
S122-stage natural gas, stainless steel heat exchanger, 120 MBH input (sizes 037–102)
S162-stage natural gas, stainless steel heat exchanger, 160 MBH input (size 061)
S182-stage natural gas, stainless steel heat exchanger, 180 MBH input (sizes 078–150)
S242-stage natural gas, stainless steel heat exchanger, 240 MBH input (sizes 120, 150)
P062-stage low-NOx natural gas, aluminized steel heat exchanger, 60 MBH input (sizes 037, 049)
P082-stage low-NOx natural gas, aluminized steel heat exchanger, 80 MBH input (sizes 037, 049, 061)
P122-stage low-NOx natural gas, aluminized steel heat exchanger, 120 MBH input (sizes 037–102)
P162-stage low-NOx natural gas, aluminized steel heat exchanger, 160 MBH input (size 061)
P182-stage low-NOx natural gas, aluminized steel heat exchanger, 180 MBH input (sizes 078–150)
P242-stage low-NOx natural gas, aluminized steel heat exchanger, 240 MBH input (sizes 120, 150)
Q062-stage low-NOx natural gas, stainless steel heat exchanger, 60 MBH input (sizes 037, 049)
Q082-stage low-NOx natural gas, stainless steel heat exchanger, 80 MBH input (sizes 037, 049, 061)
Q122-stage low-NOx natural gas, stainless steel heat exchanger, 120 MBH input (sizes 037–102)
Q162-stage low-NOx natural gas, stainless steel heat exchanger, 160 MBH input (size 061)
Q182-stage low-NOx natural gas, stainless steel heat exchanger, 180 MBH input (sizes 078–150)
Q242-stage low-NOx natural gas, stainless steel heat exchanger, 240 MBH input (sizes 120, 150)
E03Electric heat, 3 kW (size 037)
E06Electric heat, 6 kW (sizes 037, 049, 061)
E09Electric heat, 9 kW (sizes 037–102)
E15Electric heat, 15 kW (sizes 037, 049, 061)
E18Electric heat, 18 kW (sizes 078–150)
E20Electric heat, 20 kW (sizes 049, 061)
E24Electric heat, 24 kW (sizes 061–150)
E36Electric heat, 36 kW (sizes 078–150)
E54Electric heat, 54 kW (sizes 120, 150)

5167795-YTG-O-0120, page 3

Position 9 Blower option

BStandard static
DHigh static
EVFD/VAV, standard static
GVFD/VAV, high static
HVFD/VAV with bypass, standard static
KVFD/VAV with bypass, high static
LVAV, customer-supplied VFD, standard static
NVAV, customer-supplied VFD, high static
PIntelliSpeed VFD, standard static
RIntelliSpeed VFD, high static
SIntelliSpeed VFD with bypass, standard static
UIntelliSpeed VFD with bypass, high static
VIntelliSpeed, customer-supplied VFD, standard static
XIntelliSpeed, customer-supplied VFD, high static

5167795-YTG-O-0120, page 3

Position 10 Voltage

2208/230-3-60
4460-3-60
5575-3-60

5167795-YTG-O-0120, page 3

Position 11 Outdoor air option

ANo economizer
BEconomizer with barometric relief
DEconomizer with power exhaust
HMotorized damper

5167795-YTG-O-0120, page 3

Position 12 Service options

1None
2Disconnect switch
3Non-powered convenience outlet
4Powered convenience outlet
5Disconnect switch and non-powered convenience outlet
6Disconnect switch and powered convenience outlet

5167795-YTG-O-0120, page 3

Position 13 Sensors

ANone
BPhase monitor
CDirty filter switch
DSupply-air smoke detector
EReturn-air smoke detector
FPhase monitor and dirty filter switch
GPhase monitor and supply-air smoke detector
HPhase monitor and return-air smoke detector
JDirty filter switch and supply-air smoke detector
KDirty filter switch and return-air smoke detector
LSupply- and return-air smoke detectors
MPhase monitor, dirty filter switch and supply-air smoke detector
NPhase monitor, dirty filter switch and return-air smoke detector
PPhase monitor and supply- and return-air smoke detectors
QDirty filter switch and supply- and return-air smoke detectors
RPhase monitor, dirty filter switch and supply- and return-air smoke detectors

5167795-YTG-O-0120, page 3

Position 14 Controls option

AStand-alone Smart Equipment control
CSmart Equipment with BACnet MS/TP, Modbus, N2 communication card
DCPC controller, dirty filter switch, air proving switch
GNovar UCM controller, dirty filter switch, air proving switch
HHoneywell Excel 10 controller, dirty filter switch, air proving switch
MVerasys single zone
NVerasys changeover bypass
PVerasys VAV

5167795-YTG-O-0120, page 3

Position 15 Refrigeration

AStandard refrigeration
BE-coated condenser coil
CE-coated evaporator coil
DHot gas bypass
FE-coated condenser and evaporator coils
GE-coated condenser and evaporator coils, hot gas bypass
JE-coated condenser coil, hot gas bypass
ME-coated evaporator coil, hot gas bypass

5167795-YTG-O-0120, page 3

Position 16 Additional options (filters, coil guard)

1Standard 2 in. throwaway filters
22 in. pleated filters, MERV 8
34 in. pleated filters, MERV 13
4Coil guard, standard filters
52 in. pleated filters, coil guard
64 in. pleated filters, coil guard

5167795-YTG-O-0120, page 3

Position 17 Cabinet options

AStandard cabinet
EStainless steel drain pan
RReverse drain pan

5167795-YTG-O-0120, page 3

Position 18 Product generation

1First generation
2Second generation
3Third generation (listed for ZJ and ZR in the June 2020 revision)

5167795-YTG-O-0120, page 3; 5167795-YTG-Q-0620, page 3

Notes and limits

  • Covers ZH, ZJ and ZR units, sizes 037–150 (3–12.5 tons), in the 18-character model number. ZH is the standard-efficiency line at 3–5 tons and the high-efficiency line at 6.5–12.5 tons; it is not a heat pump. ZJ is high efficiency; ZR is standard efficiency with reheat.
  • The January 2020 guide (Rev. O) covers all three lines and product generations 1 and 2. The June 2020 revision (Rev. Q) drops ZH and the single-stage gas heat types and adds generation 3 for ZJ and ZR.
  • Single-stage gas heat (heat type H, J, K or L) is shown only on the 3–5 ton physical data; 2-stage gas (N, S, P or Q) runs across all sizes. The heat type (digit 6) and heat size (digits 7–8) are decoded together because the same size code means gas input for gas heat and kilowatts for electric heat.
  • Filters are the factory 2 in. throwaway filters (MERV 3) from the physical data tables. The optional 2 in. pleated MERV 8 filters are the same size; the optional 4 in. pleated MERV 13 filters have the same face size, 4 in. deep. At 6.5 and 7.5 tons the ZJ takes 24 x 20 filters while the ZH and ZR take 24 x 16. Confirm against the rack in the unit.
  • Older Predator ZH, ZJ and ZR units (for example York's 2014 seventh-generation technical guide, 528150-YTG-V-1014) use a different 19-character model number with the gas heat code given as output MBH and an airflow code in position 9. If the heat code reads N10, N15, N20, S10, S15, S20 or starts with A or B (for example A07), you are looking at that older format: this decoder does not cover it and the positions after the heat code will not line up.
  • York's sample model on the nomenclature page shows A in the blower position, which its blower table does not list; the example here uses B (standard static).
  • The 15–25 ton ZJ and ZR Series 20 units (sizes 180–300) use a different York document and are not decoded here. Neither are the York Sun Core ZX, ZY, ZQ and ZL lines.
  • No serial-number date decoder: we found no York or Johnson Controls document that states the serial format for these units.

Keep the model and serial with the unit

BoltWright keeps every rooftop’s model, serial, history and open findings with the building, so the next tech starts with what the last one knew. Capture works without reception.

Start a free service report

See BoltWright →

Not the one who picks the software? Send it to whoever runs the shop.

BoltWright put this page together from the manufacturer’s published documents, and we aren’t affiliated with York (Johnson Controls). Check the unit’s nameplate and the current York (Johnson Controls) literature before you order parts.